Captive
Aire System 1-2-3
|
|
The "System
1-2-3" is comprised of a UL Listed utility cabinet, a UL
Listed pre-piped fire protection system and a UL Listed pre-wired
fan and light electrical control panel. The fire protection
and electrical control components are contained in the utility
cabinet. Following are the components which comprise the
"System 1-2-3":
 |
The Utility Cabinet .
. .
The utility cabinet is UL Listed for
integral left or right side mount on the Captive Aire
Systems ventilation hood. It is welded directly to
the hood and fabricated of the same material as the
hood. To conceal fire extinguishing and wiring
apparatus , the fire cabinet is equipped with a full
length removable door with a center handle. UL tests
confirm temperatures do not exceed 120°F inside the
cabinet during a fire condition. (120°F is the
maximum allowed storage temperature for the UL Listed fire
suppression system and the UL Listed Industrial control
panel.) |
 |
The Pre-Piped Fire
Protection System . . .
The fire extinguishing system is a
pre-engineered distribution network. The
extinguishing agent is a low pH liquid non-corrosive
type. The system is capable of automatic detection
and activation or manual activation through a remote
manual pull station. It is Listed with Underwriters
Laboratories, Inc. The tank(s) can be contained in
the Captive Aire UL Listed utility cabinet with a full
length removable door and center handle which become an
integral part of the canopy. The system is
completely factory pre-piped by trained personnel in
accordance with UL 300, NFPA #96, #17 and #17A. All
exposed fittings are chrome plated and exposed piping is
covered with heavy gauge stainless steel sleeving.
System is capable of fuel shut down upon discharge.
A mechanical or electrical gas valve can be
provided. A micro switch is provided for connection
to the pre-wire package for the automatic shut down of
supply air fans in the event of system discharge.
Field hookup and testing will be subcontracted by Captive
Aire to a qualified and insured fire system distributor
and will be performed after hood installation. A CAD
GENERATED DRAWING WILL BE CUSTOM PRODUCED FOR EACH
INSTALLATION, indicating all drop locations and piping
schematic in accordance with local requirements. As
provided under Section 16, electrical wiring requirements
to be provided by the jobsite Electrical Contractor.
Inspections and routine
maintenance at the specified 6-month intervals shall
become the responsibility of the customer. The basic
fire system components shall include:
- Automan Release Assembly: Actuates
extinguishing system, shuts down cooking equipment, supply
fan and fuel supplies.
- Agent Tank: Contains the special liquid fire
extinguishing agent.
- Detectors: Fuse link spaced throughout the
hood(s) to activate the automan in case of fire.
- Nozzles: Placed throughout the hood(s)
according to cooking equipment and system guidelines, the
nozzles direct the extinguishing agent onto the fire
hazard areas such as the ducts, plenum and cooking
equipment.
- Pull Station: Mounts near the kitchen exit
and allows manual activation of the fire system.
|
 |
The Electrical
Control Panel . . .
The control panels, three phase or
single phase, are available in various sizes depending on
the number of fans controlled by the panel. The
control panel and the control switching have 3 mounting
location options:
- Inside the hood's UL Listed utility cabinet with
the switches face mounted on the utility cabinet.
- On top of the hood (only if the top of the hood is
accessible and allows access to the control panel.)
- Inside a stainless steel box wall mounted
(recessed or surface mounted) with the switches mounted on
the face of the stainless steel box. (All control
connections must be field wired with this option.)
All control panels
feature the following:
- Color coded wiring.
- Numbered terminal blocks.
- Grounding bar.
- Spare terminals controlled by the fire system
micro switch.
- Factory pre-wiring to shut down the supply fans in
a fire condition.
- Factory pre-wiring Option to turn on the exhaust
fans in a fire condition
- Red pilot lighted fan switch which illuminates
when turned on; enclosed in flexible conduit or EMT.
- Wiring diagram.
- Relays and/or starters.
All control panels are thoroughly tested before leaving
the factory. For most applications, the electrical
controls panels are UL Listed.
Field Wiring
Requirements:
- The motor power, single or three phase, to the
control panel.
- The motor wire from the control panel to the
lights.
- The power to the control panel for the lights.
- The control panel circuit power.
- The wiring from the control panel to the lights,
and fire system micro switch (if the control panel is wall
mounted).
|
 |
Single Phase Control
Panels . . .
The maximum horse power for a 120V
is 1-1/2 HP; the maximum horse power for a 220V is 2
HP. The minimum NEMA control box dimensions are
8" x 8" x 4", with 1/2" and 3/4"
knockouts. |
 |
Three Phase Control
Panels . . .
The minimum NEMA control box
dimensions are 12" x 18" x 6", with
1-1/2" and 3/4" knockouts. The motor
overloads are factory set to the size of the motors
ordered for the system. The contactor and overload
combination (Starter) are DIN rail mounted. |
|
Please check our Restaurant
Equipment World, Inc. site for an additional equipment selection of
more than 25,000 items including this same type of equipment.
All orders are processed via Restaurant
Equipment World, Inc. Restaurant Equipment World, Inc. sells high
quality restaurant equipment at discount prices and has more than 20 years
experience in the business. Upon clicking on a product you will be
automatically transferred to the Restaurant Equipment World, Inc. website
for SECURE
processing.
Want to
order by phone? CALL US!
1-800-821-9153
Thank you for your interest in
HoodFanWorld.Com!
Please come back
and visit us soon!
For general sales information, send mail to: sales@rewonline.com
Hood
Fan World Site Map
We Sell restaurant equipment,
hoods, fans, restaurant hood, larkin, restaurant fan, roof, ventilator,
kitchen equipment, exhaust, air, smoke, kitchen, commercial restaurant
equipment, used restaurant equipment |